{"product_id":"primary-air-insulated-switchgear-mcset-17-5kv-incomer-or-feeder-functional-unit-up-to-17-5kv-up-to-4000a-40ka-width-700mm","title":"Primary Air Insulated Switchgear, MCSet 17.5kV, incomer or feeder functional unit, up to 17.5kV, up to 4000A, 40kA, width 700mm","description":"\u003cp\u003e\u003cstrong\u003eSpecifications\u003c\/strong\u003e\u003cbr\u003eMain\u003cbr\u003eMaster range    SeT Series\u003cbr\u003eRange of product    MCSeT\u003cbr\u003eProduct name    MCSet 17.5 kV\u003cbr\u003eDevice short name    AD2\u003cbr\u003eFunctional unit    Incomer\u003cbr\u003eFeeder\u003cbr\u003eProduct or component type    Cubicle\u003cbr\u003eInsulation technology    Air insulated switchgear\u003cbr\u003eNumber of phases    3\u003cbr\u003eNetwork type    AC\u003cbr\u003eType of installation    Indoor\u003cbr\u003eBusbar system    Single busbar\u003cbr\u003eSwitching device    Vacuum circuit breaker\u003cbr\u003eProduct compatibility    EasyPact EXE\u003cbr\u003eStandards    IEC 62271-200\u003cbr\u003eRated voltage (Ur)    17.5 kV\u003cbr\u003eRated short-duration power frequency withstand voltage (Ud) \/ Common value    38 kV\u003cbr\u003eRated lightning impulse withstand voltage (Up) \/ Common value    95 kV\u003cbr\u003eRated frequency (fr)    50\/60 Hz\u003cbr\u003eRated continuous current of busbars (Ir)    4000 A\u003cbr\u003eRated continuous current (Ir)    1250 A\u003cbr\u003eRated short-circuit breaking current (Isc)    40 kA\u003cbr\u003eRated short-circuit making current    100 kA 50 Hz\u003cbr\u003e104 kA 60 Hz\u003cbr\u003eRated short-time withstand current (Ik)    40 kA\u003cbr\u003eRated duration of short-circuit (tk)    3 s\u003cbr\u003eRated peak withstand current (Ip)    100 kA 50 Hz\u003cbr\u003e104 kA 60 Hz\u003cbr\u003eLoss of service continuity category    LSC2B\u003cbr\u003eInternal arc classification    AFL\u003cbr\u003eAFLR\u003cbr\u003eRated arc fault current (IA)    40 kA\u003cbr\u003eRated arc fault duration (tA)    1 s\u003cbr\u003eInternal arc gas evacuation    Upwards inside the room\u003cbr\u003eUpwards outside the room\u003cbr\u003ePartition class    PM\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eComplementary\u003c\/strong\u003e\u003cbr\u003eDegrees of protection provided by enclosures (IP code)    IP3X (enclosure)\u003cbr\u003eIP4X (enclosure)\u003cbr\u003eIPX1 (enclosure)\u003cbr\u003eIPX2 (enclosure)\u003cbr\u003eIP2XC (between compartments)\u003cbr\u003eDegree of protection of enclosure against external mechanical impacts (IK code)    IK07\u003cbr\u003eInstrument transformer    Current transformer\u003cbr\u003eVoltage transformer\u003cbr\u003eSurge arrester\u003cbr\u003eSensor type    TH110 thermal sensor\u003cbr\u003eCL110 environmental sensor\u003cbr\u003ePD100 partial discharges monitoring solution\u003cbr\u003eVoltage presence type    VPIS voltage presence indicating system\u003cbr\u003eVDIS voltage detecting and indicating system\u003cbr\u003eProtection relay    Easergy P3\u003cbr\u003eEasergy P5\u003cbr\u003eEasergy Sepam series 60\u003cbr\u003eEasergy Sepam series 80\u003cbr\u003eArc fault detector    Easergy Vamp 125\u003cbr\u003eCable type    Single core\u003cbr\u003eThree core\u003cbr\u003eCable cross-section    630 mm² single core\u003cbr\u003e240 mm² three core\u003cbr\u003eNumber of cables per phase    Up to 4\u003cbr\u003eMass    1000 kg\u003cbr\u003eHeight    2300 mm\u003cbr\u003e2530 mm (compact tunnel with internal exhaust)\u003cbr\u003e2770 mm (tunnel with external exhaust)\u003cbr\u003e2770 mm (tunnel with internal exhaust)\u003cbr\u003eWidth    700 mm\u003cbr\u003eDepth    1550 mm (AFL)\u003cbr\u003e1725 mm (AFLR)\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eEnvironment\u003c\/strong\u003e\u003cbr\u003eProduct certifications    Bureau Veritas (BV) Marine\u003cbr\u003eDNV Marine\u003cbr\u003eAmerican Bureau of Shipping (ABS) Marine\u003cbr\u003eLloyd’s Register (LR) Marine\u003cbr\u003eAmbient air temperature for operation    -5…40 °C\u003cbr\u003eAmbient air temperature for storage    -25…55 °C\u003cbr\u003eHumidity conditions    Average relative humidity over 24 h \u0026lt;= 95 %\u003cbr\u003eAverage relative humidity over 1 month \u0026lt;= 90 %\u003cbr\u003eOperating altitude    \u0026lt;= 1000 m\u003c\/p\u003e\n\u003cp\u003eContractual warranty\u003cbr\u003eWarranty (in months)    12\u003cbr\u003e\u003c\/p\u003e","brand":"Schneider Electric","offers":[{"title":"Default Title","offer_id":47678258118756,"sku":null,"price":0.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0748\/3791\/7796\/files\/MCSet123productimage_369_1.jpg?v=1768044931","url":"https:\/\/www.jublipower.com\/products\/primary-air-insulated-switchgear-mcset-17-5kv-incomer-or-feeder-functional-unit-up-to-17-5kv-up-to-4000a-40ka-width-700mm","provider":"Jublipower","version":"1.0","type":"link"}